Cooling
- 6 x 2.7MW chillers N+2 configuration.
- Room Air Conditioning Units (RACUs) to provide down flow chilled water system at N+25%.
- RACU with bunded floor area and water leakage detection and monitoring.
- Hot aisle/cold aisle zone design.
- 800mm raised floor design with airflow space to provide the most efficient cooling.
- Free cooling operation in winter.
- Maximum external ambient temperature of 35 degrees Celsius dry bulb.
- The in-room units will provide a full function, closed control air conditioning, with cooling, humidity and de-humidification control.