- Standard power to rack at 3.5kVA with scalable options to 5kVA
 - Single power feed of 4.15MVA in a N+2 configuration is provided into the building
 - Four static 750kVA (3,000 total kVA); 3+1 configuration
 - Two 2.5MVA diesel-powered generators fuelled to provide 80 hrs at full load
 - Battery capacity at 15 minutes at full load
 - Two to four independent power circuits per cabinet from the resilient banks of UPS on a (N+1) configuration
 
- Redundant N+1 cooling as 2 chiller systems with 4 risers
 - Maximum external ambient temperatures of 24˚C and 50% humidity
 - Hot aisle/cold aisle zone design
 - Four cooling towers
 - Over 450 mm raised floor throughout
 - 24/7 central monitoring for all HVAC and building systems
 
- Multiple bandwidth & IP connectivity options
 - Low monthly cross connect fees & choice of managed IT services inside or outside our facilities
 - Diverse external and internal fiber routes (POE & building risers), all supported with DSR-MDF-IDF high performance cabling
 - Peering with Telehouse America’s International Internet Exchanges allows you to interconnect to multiple transit providers versus connecting individually
 - Both NYIIX and LAIIX are based on Brocade carrier class and high speed platform. Public and/or private peering via VLAN services is available. Route servers are available at both locations.
 
- Gas suppression system ensures no damage to customer equipment
 - Smoke alarms with pre-action sprinklers
 - State-of-the-art leak sensors in place
 - Rooftop antenna access
 - 24/7 onsite Facility Engineering, Technical Support & Customer Assistance Centre
 
- CCTV surveillance installed throughout internal and external perimeters
 - Secured & monitored single-person point entry and physical 24/7 security personnel on-site
 - 24/7 authorized customer personnel access via regularly updated access lists with photo identification
 - Biometric security confirmation system throughout the facility
 - Separate access card required for the use of elevators to access customer colocation floor
 - Strict security processes are in place to ensure delivery and loading of goods are secure
 
- Over 450mm (18 inch) raised floor throughout
 - 2,700mm (8.85 ft) above raised floor
 - Maximum floor load of 700kg/sqm
 - Overhead power and communications cable route
 - Current PUE level at 1.69
 - Customer staging rooms available with storage space
 - Access to rooftop antenna available