- Standard power per rack at 2.5kVA with scalable options up to 5kVA
 - Power to service area received via loop distribution system
 - Redundant diesel generator with a minimum of 48 hours autonomy at full capacity
 - N+1 redundant UPS system capacity at 15 minutes fully charged
 - Availability of dual power feeds for a single rack
 
- State-of-the-art high-volume air conditioning system
 - N 1 redundant climate control configuration
 - Hot aisle/cold aisle zone design
 - 450 mm raised fl oor design with airflow space to provide the most efficient cooling
 - Average floor load at 500kg/m²
 - Independent humidity and dehumidification control system
 - Temp maintained at 22˚C±10% Humidity: 55%±10%
 - Water leakage detection system in place
 
- A carrier neutral facility offering a wide choice to all customers
 - Able to connect to all ISPs and carriers in Vietnam
 
- The fire suppression system installed uses FM-200 gas system ensuring no damage to customer equipment
 - Very early smoke detection alarms (VESDA) throughout the facility
 
- 24/7 on-site personnel monitoring security of premises
 - 24/7 CCTV surveillance cameras installed around data centre
 - Photo identification required for site access
 - 24/7 CCTV surveillance cameras installed around data centre
 - IC card issued at main reception to authorised individuals for access to customer space
 - Biometric authentication by fingerprint verification at the entrance of customer space
 
- System and network monitoring service
 - Proactive pinging and internet monitoring of customer infrastructure
 - Reporting service on network traffic and customer equipment
 - Tape/DAT backup solution
 - LAN/WAN operation
 - Planning and designing services for customer IT systems